32
PC2550 Version 1.2
[29] Communicator Format Options
Page 22
Default
1
1st Telephone Number
1
2nd Telephone Number
Enter one HEX digit from [0] to [D] for each phone number:
[0] Silent Knight/Ademco slow, 10 BPS (1400 Hz handshake) 3/1 and 4/1, 4/2 non extended format
[1] Sescoa, Franklin, DCI, Vertex, 20 BPS (2300 Hz handshake) 3/1 and 4/1, 4/2 non extended format
[2] Silent Knight fast, 20 BPS (1400 Hz handshake) 3/1 and 4/1, 4/2 non extended format
[3] Radionics, (2300/1400 Hz* handshake) 3/1, 4/2 non extended format
[4] Radionics, (2300/1400 Hz* handshake) 3/1, 4/2 non extended with parity format
[5] Sescoa super speed
[6], [7] Not used
[8] Silent Knight/Ademco slow, 10 BPS (1400 Hz handshake) 3/1 extended format
[9] Sescoa, Franklin, DCI, Vertex, 20 BPS (2300 Hz handshake) 3/1 extended format
[A]Silent Knight fast, 20 BPS (1400 Hz handshake) 3/1 extended format
[B]Radionics, (2300/1400 Hz* handshake) 3/1 extended format
[C]Radionics, (2300/1400 Hz* handshake) 3/1 extended with parity format
[D]Sescoa super speed (with identified openings/closings)
*See section [16] for Radionics Handshake Option
[30] Programmable Input and Output Options
Page 23
Note: If a printer is attached to the panel, both [0] for the 1st digit and [C] for the 2nd digit must be entered.
Default
2
Auxiliary Input Zone Enter 0, 1, 2 or 3 for options below 0,1, 2 or 3 are the
(Normally open, momentary [0] Printer attached only valid entries
closure to “Aux +”) [1] Silent 24 hour input * * Not allowed for UL
[2] Audible 24 hour input local installations
[3] Momentary key arming
2 Programmable Output Enter 1 to F for options below 1 through F are
(A 50 mA switch to ground.) [1] Ground start pulse the only valid entries
Note: A relay must be used to
[2] Utility output no access code
obtain more current.
[3] Utility output any access code
[4] Utility output Group A access code
[5] Utility output Group B access code
[6] Keypad buzzer follow mode
[7] System status (arm/disarm) output
[8] Strobe output (latched alarm output)
[9] Failure to communicate output
[A] TLM and alarm
[B] Courtesy pulse
[C] Printer attached
[D] 2nd line slave
[E] Kissoff output
[F] Remote operation
(DLS-1 version 4.0 or later)
Note: Section [31]...[34] are used for split arming or split reporting only.
[31] Zone Group A Assignment
Page 23
Default
On
Zone Light 1
On Zone Light 2
On
Zone Light 3
On Zone Light 4
On
Zone Light 5
On Zone Light 6
On Zone Light 7
On
Zone Light 8
Note:
If zone light is on that zone is assigned to
Group A.
If light is on in sections [31] and [32], the zone is
common to both sides and will only be armed if both
sides are armed.
It is necessary to program a format for
each option.