DSC PC255O Specifikace Strana 5

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 44
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 4
5
panel. Connect all yellow wires from the keypads to the
“YEL” terminal on the panel. Connect all red wires from
the keypads to the “RED” terminal. Connect all black
wires from the keypads to the “BLK” terminal.
Power-up Procedure
If the keypads are located a distance from the panel,
install an extra keypad temporarily at the panel during
power up testing. An extra keypad with a short length of
cable and alligator clips attached is helpful for testing and
programming PC2550 systems.
Connect the transformer, wait approx. 5 seconds.
Enter a few keypad commands and open a zone to be
sure that the panel and keypad are responding to signals.
If the keypad does not respond and there are no
indicators on, check for AC voltage at the “AC” terminals.
If there is 16 VAC present, check that the keypad wiring
is correct and check the keypad/auxiliary supply fuse. If
the keypad/auxiliary supply fuse is blown check for a
short between the keypad red and black wires before
replacing the fuse.
If the keypad is responding normally, connect the battery.
The red battery lead attaches to the positive battery post
and the black battery lead attaches to the negative
battery post.
Note : THE PC2550 WILL NOT START UP IF ‘AC’ IS OFF
AND THE BATTERY IS LOW.
Testing The System
See Installer’s test - [] [6] [Master Code] [0] (page 9), or
do the following. Contact the monitoring station to request
a transmission test. Plug the telephone cord into the
RJ31-X jack. If a DTS-1 is being used to monitor
communicator transmissions, connect as described in
“Bench Testing” section and place the DTS-1 in the line
mode by pressing the red “LINE/LOCAL” button. Arm the
panel, wait for the exit delay to expire and trip a detector
on an instant circuit. Wait for the communication to
complete. Disarm panel and check with the monitoring
station to confirm the transmission. Perform additional
transmissions required by the monitoring station.
Check the “Trouble” light on the keypad. If it is on, press
[] then [2] to determine if there is a system trouble. The
“Trouble Display” section in “Keypad Commands” gives a
description of the different trouble conditions.
Instructing End-User
Fill out the system reference guide in the PC2550
Instruction Manual. Check off sections in the manual
which apply to the user’s system and make additional
notes if necessary.
Describe the system to an authorized user. Describe
arming and disarming procedures. Describe the basic
keypad functions. Assist the user in working through
examples of each type of command.
Provide user(s) with the Instruction Manual and instruct
them to read the manual to become familiar with the
system operation.
Instruct the user to test the system on a regular basis as
described in the Instruction Manual. The Master Code
should be changed from the default setting and recorded
in the Instruction Manual.
the [#] key. To determine the nature of the trouble, press
[][2]. (See the “Trouble Display” section.)
Zone Input Terminals “Z1” to “Z8”
Zone inputs “Z1” to “Z8” are supervised end of line
(E.O.L.) resistor circuits. Each input must be terminated
with a 1K ohm E.O.L. resistor. An alarm condition will be
created if a normally open contact is used to short across
the E.O.L. resistor. An alarm is also created if normally
closed contacts, wired in series with the E.O.L. resistor,
are opened. See the wiring diagram for normally open
and normally closed contact connection. The type of
circuit or zone definition (delay, instant, 24 hour etc.) is
programmed from the keypad using the [][8] Installer’s
Programming commands ("Programming Guide" section
[14]).
Note: For UL installation, zone inputs must be
terminated with normally closed initiating devices or
end of line resistors.
Telephone Terminals “TIP”, “RNG”, “T-1” and “R-1”
The wires from the RJ31-X telephone jack are connected
to these terminals in the following way.
TIP Green wire
Incoming line from
RNG Red wire
telephone company
T-1 Brown wire
Outgoing line to
R-1 Grey wire
house telephone(s)
Note: Ensure that plugs and jacks meet the dimension,
tolerance and metallic plating requirements of 47
C.F.R. Part 68, Subpart F.
For proper operation there must be no other telephone
equipment connected between the control panel and
the telephone company's facilities.
Do not connect the alarm panel communicator to
telephone lines intended for use with facsimile (FAX)
machines. These lines may incorporate a voice filter
which disconnects the line if other than FAX signals
are detected, resulting in incomplete transmissions.
Battery Connections
Do not connect the battery or the transformer until the
wiring is complete. Connect the red battery lead to the
positive battery terminal and the black lead to the
negative battery terminal. If the connection is made in the
reverse the battery fuse will fail. The battery charging
voltage is factory adjusted for 13.8 volts and normally
needs no adjustment. If the battery charging voltage is
out of adjustment contact your service representative.
Note: The battery charging voltage must not be
adjusted on UL listed systems.
Keypad Installation
Mount the keypads near the exit-entry doors. The
PC2550RK keypad has a red, a black, a green and a
yellow wire on the back. Connect these four wires to the
four keypad terminals on the control panel using four
conductor (quad) telephone wire. Up to three keypads
may be connected to one PC2550. Connect all green
wires from the keypads to the “GRN” terminal on the
Zobrazit stránku 4
1 2 3 4 5 6 7 8 9 10 ... 43 44

Komentáře k této Příručce

Žádné komentáře