5.2 Programming Worksheets
43
[501]- [554]Programmable Output Attributes
Program only the following attributes for the PGM options listed. All others will be ignored. PGM options are programmed in [009],
[010] & [011].
PGM Attribute Defaults (Y = Attribute ON; N = Attribute OFF):
Attribute: 12 3 4 5 678
ON
Not used Not used True Output Follows Timer Code Req. Not used Not used Not used
OFF
— — Inverted On / Off No Code Req. — — —
PGM Option
[01] Residential Burglary / Fire Bell Output
Y
[02] For Future Use
[03] Sensor Reset [4][7][2]
YN
[04] 2-Wire Smoke Support (PGM2 only)
Y
[05] System Armed Status
Y
[06] Ready To Arm
Y
[07] Kypad Buzzer Follower Mode
Y
[08] Courtesy Pulse
Y
[11] System Tamper (all sources, zones, keypad, modules)
Y
[12] TLM and Alarm
Y
[13] Kiss-off Output
YY
[14] Ground Start Pulse
YY
[15] Remote Operation (DLS Support)
YY
[16] For Future Use
Y
[17] Away Armed Status
Y
[18] Stay Armed Status
Y
[19] Command Output #1, [4][7][1]
YY Y
[20] Command Output #2, [4][7][2]
YY N
[21] Command Output #3, [4][7][3]
YY N
[22] Command Output #4, [4][7][4]
YY N
[23] 24 Hr Silent Input (PGM2 only)
Y
[24] 24 Hr Audible Input (PGM2 only)
Y
[25] Delayed Burglary & Fire Output
Y
[30] Partition Status Alarm Memory Output
Y
Attribute:
123456 7 8
PGM Option
ON Serv. req. AC Fail TLM Fault FTC Zone Fault Zone Tmp. Zn. Low Bat. Loss of Clock
OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled
[09] System Trouble
YYYYYY Y Y
ON Burg. Evnt. Fire
Evnt.
Panic Evnt. Med. Evnt. Supv. Evnt. Priority Evnt. Holdup Evnt. Follows Timer*
OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Latched
[10] System Event
YYYYYYY N
*If attribute [8] is turned ON, attributes [1-7] must also be turned ON.
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8
[29] Zone Follower
NNNNNNN N
Komentáře k této Příručce