DSC Power832 PC5O15 Instalační manuál

Procházejte online nebo si stáhněte Instalační manuál pro Bezpečnostní systémy pro řízení přístupu DSC Power832 PC5O15. DSC Power832 PC5O15 Installation manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 48
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
PC5O15
Version 2.2
DLS-3 version 1.3 or higher
WW
WW
W
ARNINGARNING
ARNINGARNING
ARNING
This manual contains information on limitations regarding product
use and function and information on the limitations as to liability of the
manufacturer. The entire manual should be carefully read.
Installation
Manual
WITH
Zobrazit stránku 0
1 2 3 4 5 6 ... 47 48

Shrnutí obsahu

Strany 1 - Installation

PC5O15Version 2.2DLS-3 version 1.3 or higherWWWWWARNINGARNINGARNINGARNINGARNING This manual contains information on limitations regarding pro

Strany 2 - WARNING Please Read Carefully

G E T T I N G S T A R T E D7Connect the PC5015 and modules that use the telephone line(s) in the following order:For example, if you are installing a

Strany 3 - Table of Contents

G E T T I N G S T A R T E D8BELL: 700 mA. Continuous Rating.3.0 A. Short Term. Available only with stand-by battery connected.• PC5200/5204 VAUX:1.0

Strany 4 - System Introduction

G E T T I N G S T A R T E D92.7 Keypad AssignmentThere are 8 available addresses for keypads. The LED, LCD5501Z and the LCD5501Z32-433 keypads by def

Strany 5 - 1.2 Additional Devices

G E T T I N G S T A R T E D102.9 Removing ModulesIf a module is no longer required on the system the panel must be told to no longer supervise the mo

Strany 6

G E T T I N G S T A R T E D11The following chart shows zone status under certain conditions:Loop Resistance Loop Status0Ω (shorted wire, loop shorted

Strany 7 - 1.3 Out of the Box

G E T T I N G S T A R T E D122.10.8 LINKS Supervisory (24 Hour Supervisory)When using the LINKS1000 cellular communicator, any main board zone maybe

Strany 8 - Getting Started

Keypad CommandsS E C T I O N 313All keypads provide complete information and control of the alarm panel. The panel can be completely programmedvia an

Strany 9

K E Y P A D C O M M A N D S14system was not Ready. When the correct code is entered and the system is Ready the panel will beep six timesrapidly and

Strany 10 - G E T T I N G S T A R T E D

K E Y P A D C O M M A N D S15The various troubles are described below:Light Trouble1 Service Required: Press [1] to determine the specific trouble. I

Strany 11

K E Y P A D C O M M A N D S16[✱✱✱✱✱] [5] Programming Access CodesAll 37 access codes are programmed in this section. For instructions on programming

Strany 12 - 2.8 Enable Supervision

LIMITED WARRANTYDigital Security Controls Ltd. warrants the original purchaser that for a period of twelve months fromthe date of purchase, the produc

Strany 13

K E Y P A D C O M M A N D S17[✱✱✱✱✱] [0] Quick ArmIf the Quick Arm Enable option is enabled the panel can be armed by entering [✱][0]. This is a usef

Strany 14

K E Y P A D C O M M A N D S18[06] - [✱]+[4] Door Chime On/OffThis function key provides the user a simple method for turning the Door Chime feature o

Strany 15 - 2.11 Keypad Zones

K E Y P A D C O M M A N D S19[24] - Recall Bypass Group #1This function key will recall zones in Bypass Group #1. This group is programmed by the use

Strany 16 - Keypad Commands

How to ProgramS E C T I O N 420The following section of the manual describes how to enter Installer Programming and how to program the varioussection

Strany 17 - 3.4 [✱] Commands

H O W T O P R O G R A M21Example: for the three digit account number ‘403’, you would enter [4], [✱] [1] [✱] [3], [0].[4] to enter the digit 4[✱] to

Strany 18 - (See Section 5.2 “Zone

Program Descriptions22S E C T I O N 5The following section explains all the programmable features including how the feature operates, options thatper

Strany 19 - K E Y P A D C O M M A N D S

P R O G R A M D E S C R I P T I O N S23[09] 24 Hour Supervisory Zone If this zone is violated, whether armed or disarmed, the panel will report to t

Strany 20 - 3.5 Function Keys

P R O G R A M D E S C R I P T I O N S24Force Arm Enable Determines if the system can be armed with the zone violated. At the end of exit delay, if

Strany 21

P R O G R A M D E S C R I P T I O N S251st Phone Number ... Section [301]2nd Phone Number ...

Strany 22

P R O G R A M D E S C R I P T I O N S26Please refer to Appendix A: “Reporting Codes”for a list of Contact ID Identifiers.Contact ID Uses Programmed/A

Strany 23 - How to Program

Table of ContentsSection 1: Introduction1.1 PC5015 Specifications ... 11.2 Additional Devices ..

Strany 24 - 4.5 Viewing Programming

P R O G R A M D E S C R I P T I O N S275.7 Communicator – Reporting CodesReporting codes must be programmed in order for the panel to report events t

Strany 25 - Program Descriptions

P R O G R A M D E S C R I P T I O N S28on the Bell Output of the main panel. The Bell Circuit Trouble Restoral Reporting Code will be transmitted ass

Strany 26 - 5.2 Zone Attributes

P R O G R A M D E S C R I P T I O N S29The time to complete a successful download can be significantly reduced with the use of the PC-Link. This adap

Strany 27 - 5.3 Communicator - Dialing

P R O G R A M D E S C R I P T I O N S30Please refer to the Control Panel Wiring Diagram in this manual for wiring instructions.Only ONE of options [0

Strany 28

P R O G R A M D E S C R I P T I O N S31[15] Remote Operation (DLS-3 Support) This output can be activated and deactivated remotely using DLS soft

Strany 29

P R O G R A M D E S C R I P T I O N S32PGM Output Attributes ... Section [141]-[142]PC5208 Attributes ...

Strany 30

P R O G R A M D E S C R I P T I O N S33Test Transmission Reporting Codes ... Section [352]Test Transmission Time of Day ...

Strany 31 - 5.8 Downloading

P R O G R A M D E S C R I P T I O N S34exists. (See Section 5.17 “Swinger Shutdown”.)The event buffer can be viewed three different ways. It can be v

Strany 32 - 5.10 Programmable Outputs

P R O G R A M D E S C R I P T I O N S35Arm/Disarm Bell Squawk ... Section [014], Option [1]Bypass Status Display

Strany 33

P R O G R A M D E S C R I P T I O N S365.23 Keypad BlankingIf the Keypad Blanking Option is enabled the panel will turn off all lights and LCDs o

Strany 34

1System IntroductionS E C T I O N 11.1 PC5015 SpecificationsFlexible Zone Configuration:• 8 Fully Programmable Zones• 38 Access Codes: 32 User, 1 Sys

Strany 35 - 5.13 Test Transmission

P R O G R A M D E S C R I P T I O N S375.26.4 LINKS Special PreambleIn some areas of North America, dialing #DAT or ✱DATA reduces the cellular billin

Strany 36 - 5.16 Event Buffer

P R O G R A M D E S C R I P T I O N S385.28.2 Factory Default Main Panel (Software) and other ModulesStep 1 - Enter Installer Programming.Step 2 - En

Strany 37 - 5.19 Keypad Backlighting

SIA Format (Level 2—Hardcoded)This format will send the Account Code along with itsdata transmission. At the receiver, the transmissionwould look simi

Strany 38 - 5.22 Keypad Lockout

40REPORTINGV CODESSection#Reporting Code Code Sent When... DialerDirection*Auto-maticContactIDSIA AutoRepCodes**[344-348]Openings system disarmed (use

Strany 39 - 5.25 Keypad Tampers

41Zone Definition SIA Auto RepCodes**Delay, Instant, Interior, DelayStay/Away, Interior Stay/Away,24-hr Burg.BA-ZZ/BH-ZZStandard 24-hr Fire, Delayed 2

Strany 40 - 5.28 Default (Factory)

42PC5015 Control Panel Wiring DiagramAPPENDIXV C

Strany 41 - 5.30 Walk Test (Installer)

Modules Supported on the PC5015 v2.2APPENDIXV DeludoMdetroppuSstnemmoC0855trocsEseY4025CPseY8025CPseY8015CPseYL8015CPseYX.1v2315CPseYsdapyeKdlehdnaHro

Strany 42 - Reporting Codes

FCC COMPLIANCE STATEMENTCAUTION: Changes or modifications not expressly approved by Digital Security Controls Ltd. could void your authority to use th

Strany 43 - REPORTINGV CODES

©2002 Digital Security Controls Ltd.Toronto, Canada • www.dsc.comTechnical Support: 1-800-387-3630Printed in Canada 29003272 R005Direct all comme

Strany 44 - Zone Reporting Codes

S Y S T E M I N T R O D U C T I O N2False Alarm Prevention Features• Audible Exit Delay • Audible Exit Fault • Urgency on Entry Delay• Quick Exit • S

Strany 45 - APPENDIXV C

S Y S T E M I N T R O D U C T I O N31.2.4 PC5200/PC5204 Power Supply Output ModuleThe PC5200 and PC5204 can provide up to 1 Amp of additional power f

Strany 46

S Y S T E M I N T R O D U C T I O N41.2.11 PC5700 Fire ModuleThis is a zone expansion module with four general purpose zone inputs, two Class Asuperv

Strany 47

Getting StartedS E C T I O N 25The following sections provide a complete description of how to wire and configure devices and zones.2.1 Installation

Strany 48

G E T T I N G S T A R T E D6Auxiliary Power Terminals - AUX+ and GNDThese terminals provide up to 550 mA of additional current at 12 VDC for devices

Komentáře k této Příručce

Žádné komentáře