32
[010] PC5208 PGM Output Programming (PGM 3-10) (Section 5.11 “PGM Output Options” )
Default Default
01 I_______I_______I PGM 3 01 I_______I_______I PGM 7
01 I_______I_______I PGM 4 01 I_______I_______I PGM 8
01
I_______I_______I PGM 5 01 I_______I_______I PGM 9
01
I_______I_______I PGM 6 01 I_______I_______I PGM 10
Program PGM Option Attributes in sections [143] - [150].
[011] PC5204 PGM Output Programming (PGM 11-14)
(Section 5.11 “PGM Output Options” )
Default Default
01
I_______I_______I PGM 11 01 I_______I_______I PGM 13
01
I_______I_______I PGM 12 01 I_______I_______I PGM 14
Program PGM Option Attributes in sections [151] - [154].
[012] Keypad Lockout Options
(Section 5.21 “Keypad Lockout Options” )
NOTE: If Keypad Lockout is active, the panel cannot be dis-
armed with a keyswitch.
Default
000
I_______I_______I_______I Number of Invalid Codes Before Lockout (001-255 codes)
000 I_______I_______I_______I Lockout Duration (001-255 minutes)
[013] First System Option Code
Default Option ON Off Section
OFF
I________I 1 Normally Closed Loops End-of-Line Resistors 2.11
OFF
I________I 2 Double End-of-Line Resistors Single End-of-Line Resistors 2.11
ON* I________I 3 Panel Shows All Troubles When Armed Panel Shows Only Fire Troubles When Armed 3.4
OFF I________I 4 Tampers/Faults Do Not Show As Open Tampers/Faults Show As Open 3.4
OFF
I________I 5 For Future Use
ON I________I 6 Audible Exit Fault Enabled Audible Exit Fault Disabled 5.18
ON I________I 7 Event Buffer Follows Swinger Shutdown Event Buffer Logs Events Past Shutdown 5.20
OFF
I________I 8 Temporal Three Fire Signal Enabled** Standard Pulsed Fire Signal 5.13
* Option 3 must be OFF if LCD keypads older than v2.0 are used.
**The Temporal Three Fire Signal option must be used for UL Household Fire installations.
[014] Second System Option Code
Default Option ON Off Section
OFF
I________I 1 Arm / Disarm Bell Squawk enabled Arm / Disarm Bell Squawk disabled 5.17
OFF
I________I 2 Bell Squawk During Auto Arm No Bell Squawk During Auto Arm 5.18
OFF I________I 3 Bell Squawk On Exit Delay No Bell Squawk On Exit Delay 5.18
OFF I________I 4 Bell Squawk On Entry Delay No Bell Squawk On Entry Delay 5.18
OFF
I________I 5 Bell Squawk On Trouble No Bell Squawk On Trouble 3.4
ON I________I 6 Audible Exit with Urgency Silent Exit Delay 5.18
OFF I________I 7 Exit Delay Termination Enabled Exit Delay Termination Disabled 5.18
OFF
I________I 8 Fire Bell is Continuous Fire Bell Follows Bell Cut-off 5.13