PC1404 v1.0Installation GuideWARNING: This manual contains information on limitations regarding product use and function and information on the limita
PC14044Keybus Terminals – AUX+, AUX-, YEL, GRN The Keybus is used by the panel to communicate with modulesand vice versa. Each module has four Keybus
2 Installation2.5 Current Ratings – Modules & AccessoriesIn order for the PC1404 system to operate properly, the poweroutput capabilities of the
PC14046Single End Of Line (EOL) Resistors (5600)To enable panel detection of single end of line resistors, Section[013], Options [1] and [2] must be
2 Installation2.11 Fire Zone Wiring All 4-wire smoke detectors must be wired according to the fol-lowing diagram:All 2-wire smoke detectors must be w
PC140483 Keypad CommandsUse any compatible keypad to enter commands and/or program the PC1404 security system. The LED keypad uses function and zonein
3 Keypad Commands9[][7][x] Command Functions 1–4[][8][Installer Code] Installer Programming[][9][User Code] No-Entry Arming[][0] Quick Arm (disar
PC140410[*][3] Alarm MemoryWhen Disarmed, press [*] then [3] to enter the alarm memory mode. The "Memory" light will flash and any alarm cau
3 Keypad Commands11[7] Bell Squawk upon Arming/Disarming – This attribute is used to determine whether an access code should generate an arming/dis-ar
PC140412Additional Keypad FunctionsThe following additional keypad functions are available:Event Buffer: View the 128-event panel bufferBrightness Con
4 Programming134 ProgrammingThe PC1404 can be programmed using the following methods:4.1 Installer ProgrammingThe following section of the manual desc
i6$)(7<,16758&7,216IRU6(59,&(3(56211(/WARNING: When using equipment connected to the TELEPHONE NETWORK, there are basic safety instruct
PC140414If you are using a pulse communications format, a decimal zero [0] does not transmit. Programming a zero [0] tells the panel not to sendany pu
5 Programming Worksheets155 Programming Worksheets5.1 Index to Programming Worksheets and Descriptions Programming Option
PC1404 165.2 Programming WorksheetsKeypad Partition/Slot and Function Key Programming[000] Function Key ProgrammingNote: Keypad enrollment must be don
5 Programming Worksheets17[005] System Times[009] Main Board PGM Output Programming (PGM 1 & 2)[010] PC5208 PGM Output ProgrammingValid entries fo
PC1404 18[011] PC5204 PGM Output Programming[012] Keypad Lockout OptionsNote: If Keypad Lockout is active, the panel CANNOT be disarmed with a keyswi
5 Programming Worksheets19[017] Fifth System Options[018] Sixth System Options[020] Keypad Zone Assignments[022] Ninth System Options[023] Tenth Syste
PC1404 20[030] Zone Loop Response Options[101]-[108] Zone Attributes [101] Zone 1 Attributes [102] Zone 2 Attributes [103] Zone 3 Attributes [104]
5 Programming Worksheets21[170] PGM Output Timer Default 005 I_______I_______I_______I Valid entries are 001-255 seconds[175] Auto-arm Postpone TimerD
PC1404 22[176] Cross Zone/Police Code Timer Default 060 I_______I_______I_______I Valid entries are 000-255 seconds/minutes[181] Auto-Arm Time of DayD
5 Programming Worksheets23[329] Priority Alarm and Restore Reporting Codes[330] Tamper Reporting Codes, Zones 01-08 [334] Tamper Restore Reporting Cod
LL*XLGHOLQHVIRU/RFDWLQJ6PRNH&2'HWHFWRUVThe following information is for general guidance only and it is recommended that local fire co
PC1404 24[343] Opening (Disarming) Reporting Codes, Access Codes 17-32[344] Miscellaneous Opening (Disarming) Reporting Codes[345] Maintenance Alarm R
5 Programming Worksheets25[367] Opening/Closing Communicator Call Directions[375] System Maintenance Alarm/Restore Communicator Call Directions[376] S
PC1404 26[382] Third Communicator Options[383] Fourth Communicator OptionsDLS Downloading[401] Downloading Option Codes[402] DLS Downloading Computer’
5 Programming Worksheets27[404] Panel ID Code (Enter 6 Hexadecimal Digits)[405] Answering Machine Double-Call Timer Default 060 I_______I_______I_____
PC1404 28Zone Follower PGM requires 2 programming sections for attributes: the normal PGM attribute Sections [501-514] and Sections [551-564] for zone
5 Programming Worksheets29[601] Closing (Arming) Reporting Codes, Access Codes 33-40[605] Opening (Disarming) Reporting Codes, Access Codes 33-40INTER
PC1404 30Programming PK5500 KeypadsIf you have an PK5500 keypad, additional programming is required for proper operation. All LCD programming is done
Programming PK5500 Keypads31[001]-[008] Zone Labels[071] First User Display MaskDefaultZ o n e _ _ _ _ 1 _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ __BBBB_BBB
PC1404 32[072] Second User Display Mask[073] Downloaded LCD Message DurationDefault: 003 _BBBB_BBBB_BBBB_ (Valid entries are 000-255, 000=Unlimited
Programming PK5500 Keypads33[080] PGM Terminal 1[082] Local PGM Output Activation Time[101] Partition 1 Label[102]–[108] Partition 2–8 Labels[120]–[12
LLLLimited WarrantyDigital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product
PC14045.3 Programming Descriptions3URJUDPPLQJ'HVFULSWLRQVThe following is a description of the programming features and options available in t
5.3 Programming DescriptionsZone ProgrammingZones 1-8 are enabled by default. Disable unused zones or enable additional zones in Section [001] Zone
PC1404[08] Standard 24-hr Fire Zone (hardwired) Note: Do not wire Fire zones on keypad zone terminals if the DEOL supervision option is enabled for
5.3 Programming DescriptionsA bypass of this zone type must be manually removed.With an audible alarm active, using the keyswitch when disarmed is t
PC1404[005] System TimesEnter Section [005] then Subsection [01] to program the Entry Delay 1, Entry Delay 2 and Exit Delay for the system. Entries
5.3 Programming Descriptions09 System Trouble. This PGM output switches to ground when any of the selected Troubles are detected. The output de-acti
PC1404[012] Keypad Lockout OptionsThis section determines how the keypad function operates. The panel can be configured to "lockout" keypa
5.3 Programming Descriptions[013] First System Options[014] Second System OptionsOption Description[1] Zone Loop TypeON: Normally Closed Loops. All
PC1404[015] Third System Options[016] Fourth System Options[7]Exit Delay Termina-tionExit Delay Termination Enabled. The exit delay will be reduced
5.3 Programming Descriptions[017] Fifth System Options [018] Sixth System Options [3] Keypad BlankingON: Blank Keypad When Not Used. If no keys are
ivTable of ContentsSafety Instructions for Service Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PC1404[020] Keypad Zone AssignmentEnter the two-digit zone number to be assigned to each keypad assigned to a specific slot. Only one keypad can be
5.3 Programming Descriptions[030] Zone Loop Response OptionsFast loop response for the onboard zones is programmable using Installer Programming Sec
PC1404[168] Daylight Savings Time BeginsExample: E.g., Set the clock 1 hour ahead at March 5th, 2006 at 2:00am.1. Enter Section [168]. 2. Program t
5.3 Programming Descriptions[199] Auto-Arming Pre-Alert TimerIn this section, program the time (in minutes) for the Auto-Arming Pre-Alert time. This
PC1404[330]-[334] Tamper/Restore Reporting Codes, Zones 01-8These reporting codes are used by the communicator to transmit zone tampers and restores
5.3 Programming DescriptionsFire Trouble & RestoreAn open circuit or any Low Sensitivity, Tamper or Fault report from a wireless smoke detector
PC1404[348] Test Transmission Reporting CodesWalk Test Begin/EndThese reporting codes are sent when the walk test is initiated and terminated. These
5.3 Programming Descriptions[378] Test Transmission Time of DayThe panel can be configured to communicate a test transmission signal to the monitori
PC1404[381] Second Communicator Options[382] Third Communicator OptionsOption Description[1] RingbackON: Opening After Alarm Keypad Ringback Enabled
5.3 Programming Descriptions[383] Fourth Communicator Options[401] Downloading Option Codes[7] Residential DialON: Number of Dialing Attempts is 1 f
vPC1404 Wiring Diagram200–350 mA931404-112-WIRE AND 4-WIRE SMOKE DETECTORSFor NA installations only1.2, 4, 7 AhLCD5511LED5511PC1555RKZPK5500/PK5501PK5
PC1404[402] DLS Downloading Computer’s Telephone NumberThis is a 32-digit hexadecimal programming section. The downloading computer telephone number
5.3 Programming Descriptions[551-564] Extended PGM Attributes for PGM Type 29, Zone Follower [551]-[564]The following attributes are available for t
PC1404[700] Automatic Clock AdjustThe value entered here adds or subtracts seconds at the end of each day to compensate for inaccuracies in the syst
5.3 Programming Descriptions[703] Delay Between Dialing AttemptsFor standard (force) dialing, the panel will go off-hook, search for dial tone for 5
PC1404[903] View Module Supervision In this mode, the system displays all of the modules presently enrolled on the system as indicated by the corres
6 Testing & Troubleshooting6 Testing & TroubleshootingTesting:• Power up system• Program options as required (see Section 5 Programming Work
PC1404PC520X Aux Power Supply Trouble • Ensure that a the power supply aux power terminal is not shorted to ground. • Ensure that the maximum power
6 Testing & TroubleshootingTrouble [5] Zone Fault Press [5] to determine specific zones with a Fault troubleOpen circuit is present on
PC1404 Appendix A: Reporting Code FormatsThe following tables contain Contact ID and Automatic SIA format reporting codes. See Programming Sections
Appendix A: Reporting Code Formats[345]-[346] Bell Circuit Trouble/Rest. Software deactivates the bell output if a short is detectedso no additiona
1 Introduction11 IntroductionThis manual provides installation and programming informationfor the PC1404 four-zone panel security system. 1.1 Compatib
PC1404 Table 3: Automatic Zone Alarm/Restoral Codes=RQH'HILQLWLRQ 6,$$XWR5HS&RGHV&RQWDFW,'$XWR5HS&RGHV&RQWDFW,&apo
Appendix B: Communicator Format OptionsAppendix B: Communicator Format OptionsThe following format options are programmable in Section [350] Communi
PC1404 06Residential DialIf Residential Dial is programmed and an event that is programmed to communicate occurs, the panel will seize the line and
Appendix C: Regulatory Approvals InformationAppendix C: Regulatory Approvals InformationNorth America FCC COMPLIANCE STATEMENTwill provide advance n
EuropeThis product is in conformity with:EMC Directive 2004/108/EC based on results using harmonized standards in accordance with article 10(5), R&
PC14042Zone Configuration• 31 zone types and 11 programmable zone attributes• Supports up to 4 hardwired NC, SEOL, DEOL zones, expandable to 8 with th
2 Installation2 InstallationThe following sections provide a thorough description of how towire and configure devices and zones.2.1 Installation Step