G E T T I N G S T A R T E D
10
2.10.2 Single End Of Line (EOL) Resistors (5600
)
NORMALLY CLOSED
CONTACT WITH
5600 END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
NORMALLY OPEN
CONTACTS WITH
5600 END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
2 NORMALLY OPEN
CONTACT AND
2 NORMALLY CLOSED
CONTACT WITH
5600 END OF LINE
RESISTOR
1 NORMALLY OPEN
CONTACT AND
1 NORMALLY CLOSED
CONTACT WITH
5600 END OF LINE
RESISTOR
ANY Z
TERMINAL
ANY COM
TERMINAL
To enable panel detection of single end
of line resistors, programming section
[013], options [1] and [2] must be OFF.
This option should be selected
if either Normally Closed (NC)
or Normally Open (NO)
detection devices or contacts
are being used
.
End of Line Resistors ............................................. Section [013], Option [1]
Single End of Line Resistors ................................. Section [013], Option [2]
2.10.3 Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, programming section [013], option [1] must be OFF and
option [2] must be ON.
ANY Z
TERMINAL
ANY COM
TERMINAL
ALARM
CONTACT
DOUBLE EOL CIRCUIT
1 NORMALLY CLOSED
CONTACT WITH
5600 END OF LINE
RESISTORS
If the Double EOL supervision option is enabled, all hardwire zones must be wired
for Double EOL resistors, except for Fire and 24 Hour Supervisory zones.
Do not wire DEOL resistors on keypad zones.
Do not use DEOL resistors for Fire zones or 24 Hour Supervisory zones. Do not wire
Fire zones to keypad zone terminals if the DEOL supervision option is selected.
This option can only be selected if Normally Closed (NC) detection devices or
contacts are being used.
Only one NC contact can be connected to each zone. Wiring multiple detection
devices or contacts on a single loop is not allowed
.
The following chart shows zone status under certain conditions:
Loop Resistance Loop Status
0 (shorted wire, loop shorted) Fault
5600 (contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200 (contact open) Violated
End-of-Line Resistors ............................................ Section [013], Option [1]
Double End-of-Line Resistors ............................... Section [013], Option [2]
2.10.4 Fire Zone Wiring - 4 wire Smoke Detectors
All zones defined as Fire
(See Section 5.1 Zone Definitions)
must be wired according to the following diagram:
For a complete description of how fire zones operate,
see Section 5.1 Zone Definitions.
2.10.5 Fire Zone Wiring - 2 wire Smoke Detectors
If PGM2 has been programmed for 2 Wire Smoke Detector connection
(See Section 5.10 PGM Output),
the
detectors must be wired according to the following diagram:
+
+
-
For a complete description of how fire zones operate,
see Section 5.1
Zone Definitions.
If PGM2 is programmed for 2 wire smoke support, Jumper CON1
on the main board must be removed.